Q:
In fan application, should we run the variable frequency in vector control mode or v/f mode? what are the pros and cons of both the modes. what are the methods to find out the correct running of the motor?

A:
It depends on the application. If it is a small fan or easy application go with V/F. As a rule V/F is going to be less accurate, lower current and less money. You can buy a vector VFD and run it in V/F mode.

If you get into kilns with fans that are reversing and being back driven you may want vector with external braking resistors. On large fans you may not have a choice, only vector variable frequency drives, but you may need to increase the slip to reduce current.

Most VFD's have a tuning procedure you can do or you can get motor constants from motor manufacturer. I think the best is to get a VFD that constantly tunes to the conditions while running, like Gozuk.

Vectors really do well below 15 hz with speed and torque control. Vectors are used in hoists where you need torque at 0 hz. The Vector senses the motor speed and adjusts the output to match the command speed. It can sense with an external device/encoder or it can sense the slip by the current waveform compared to output voltage wave form, sensorless vector.

A V/F basically just puts out the commanded frequency and does not care about changing load or slip.
If it is a centrifugal fan then it would be cube law loaded. The HP required will increase or decrease to the cube of the speed. The motor would start with no load and the load increases to 100% at 100% speed. High starting/break away torques are usually not required. As a result the motor and variable frequency drives usually do not require an added service factor.
Most of these applications do not require high accuracy speed/flow regulation so v/f is all that is needed.
If the fan is in a test facility (like a wind tunnel) and it is necessary to control the flow or pressure accurately for extended periods while measurements are taken then the vector control mode may be required.

You may also like:

say there is a permanent fault on overhead transmission line, the distance / line differential protection should operate and trip respect circuit breaker (CB) which is feeding the fault. This protection relay ...
Variable frequency technology is a new drive technology which adopts advanced electronic technique, computer control technique and communication technique. It goes ahead of any other speed adjusting methods. ...
In the days before networked motors, all inputs were accounted for in the Input list and all outputs were accounted for in the Output list. The IO count was then evaluated to help determine the complexity of a ...
High performance variable frequency drive makes a measurement of the torque through the current to control the brake, for other it's based on speed reference. Then it depend the brake to stand still the motor ...
Variable speed drive application in purification system optimizes the system performance, improves purification effect, reduces power consumption greatly. According to related statistic, flue gas consumption ...
service VSD blog: A deep observation of automation control industry, especially in AC motor variable speed drive for industrial motor controls.

Hot Tags

Featured

7 months back I was involved in a harmonics evaluation study at Budweiser. This was one of many I've participated in over the past 20 years, basically because in facilities like ... Most of variable speed drives are applying on high temperature fans, kiln head coal mill fans, kiln head surplus fans, raw mill circulating fans and so on. Two production lines ... Variable speed drive application in purification system optimizes the system performance, improves purification effect, reduces power consumption greatly. According to related ... The motor power factor does not make a big difference other than giving an idea of loading. In regards to the variable speed drive fixing power factor everyone is mostly correct. ... A soft starter is a basic device which will ramp up the speed of your motor to full speed over a preset time, easing mechanical stress and also easing the high inrush currents ...

What's New