For high torque requirement, we need to over size both sq cage motor and variable frequency drive. Should we invest this solution? or operate the same system? sq cage Which reason sq cage motor and VFD system better than slip ring system?

Some slip-ring motors can generate a very high starting torque, much higher than torque available at the output of squirrel-cage motors inverter driven. First of all you have to state this maximum value of starting torque. Please check also if - in case of problems at start-up for excessive load - there is the possibility to rotate the crusher using a low-power gearbox with a free-wheel, or if you can reverse shortly the direction. Another possibility is the addition of an hydro-coupling between motor and load. That will really make the motor starting easy. Most hydraulic torque converter can multiply the torque. Also in a dusty environment like a cement plant, a totally enclosed induction motor will certainly last a long time.

I recommend using high efficiency induction motor with variable speed torque control. The prices of permanent magnets have increased ca 300% during last 12 months. Also, the price of special permanent magnet high torque motor will be very high too. The use of squirrel cage induction motor with frequency converter will consume much less energy compared to phase rotor induction motor with resistive slip control, which is quite probably used. The energy saving can be essential.

You have few options here:
1. Slip energy recovery with the current motor but with dual inverter on rotor side, which may not be too expensive as it is lower power on rotor side and no change in motor.
2. Slip ring motor with shorted slip ring and stator side inverter control, which may be expensive due to higher cost of electronics for the higher power rating of stator side.
3. Sq cage motor with stator side inverter control, which may be expensive because of motor replacement and higher cost of electronics for the higher power rating of stator side.

You may also like:

Converting a synchronous motor to an induction motor is easily done, to most motors, by shorting the rings, however, you would most likely need to use a properly sized VFD to get the starting torque you need. ...
If a guarantee is involved with stiff liquidated damages, then lots of testing and certification on each serial numbered unit is likely to be necessary. (not to mention the cost of law suits....). Like the ...
Due to current decrement in the Generator during fault conditions the Back-up protection with IDMT relay for a generator in the Electrical protection Scheme becomes complicated. Accordingly, the setting of the ...
The motor power factor does not make a big difference other than giving an idea of loading. In regards to the variable speed drive fixing power factor everyone is mostly correct. A variable speed drive will ...
How to measure or diagnose common mode voltage of three phase PWM variable speed drive? And how to solve EMI from motor Driver? For your first question: Could you let me know your definition of variable ...
service VSD blog: A deep observation of automation control industry, especially in AC motor variable speed drive for industrial motor controls.

Hot Tags

Featured

7 months back I was involved in a harmonics evaluation study at Budweiser. This was one of many I've participated in over the past 20 years, basically because in facilities like ... Most of variable speed drives are applying on high temperature fans, kiln head coal mill fans, kiln head surplus fans, raw mill circulating fans and so on. Two production lines ... Variable speed drive application in purification system optimizes the system performance, improves purification effect, reduces power consumption greatly. According to related ... The motor power factor does not make a big difference other than giving an idea of loading. In regards to the variable speed drive fixing power factor everyone is mostly correct. ... A soft starter is a basic device which will ramp up the speed of your motor to full speed over a preset time, easing mechanical stress and also easing the high inrush currents ...

What's New